Read the nameplate: amps, RLA and LRA for generator sizing

Every sizing chart wants your appliances in watts. Your appliances have never heard of watts; their labels speak amps. This page translates: where the numbers hide, what running amps, RLA and LRA each mean, how to turn them into the watts a generator has to carry, and what to do about the one figure almost no label prints (the starting surge). Every worked example below comes from real plates read in a real house.

Where the plate hides

If you can read the label, take a photo of it. The model number alone is often enough to pull the same figures from the manufacturer's manual online.

The numbers, translated

Nameplate terms you will meet while sizing a generator
On the plate What it is What you do with it
Running amps (sometimes FLA) The current the motor draws while doing its job. Amps × volts = running watts. This is your baseline load.
RLA (rated load amps) The compressor version of running amps, printed on AC and refrigeration plates. Same conversion: RLA × volts = compressor running watts. Add the fan amps printed beside it.
LRA (locked-rotor amps) The current the motor would pull with its rotor held still, in practice, the first-instant surge at start-up. LRA × volts = worst-case starting watts. The surge your generator must survive for a second or two.
Volts 115 or 230 on most plates. Motors are stamped for the nominal grid: 115 V plates run on 120 V service, 230 V plates on 240 V. Use the plate's own voltage in the conversion and you are within a few percent.

One warning: nameplate running amps are maximum ratings. A fridge stamped 8.5 A does not draw 8.5 A around the clock; it cycles, and the plate covers the worst case (defrost heater, ice maker, hot day). Sizing on plates is deliberately conservative; you are buying headroom, not error.

Worked examples: real plates, converted

Figures logged from real equipment in one house (and one pump manual)
Equipment Plate says Running watts Starting watts
Kitchen fridge 8.5 A @ 115 V, no LRA printed 978 ~3,070 (estimated)
Upright freezer 3.0 A running, 14.2 A LRA 360 1,704 (from LRA)
Central AC, 2-ton 13.5 A RLA + 0.5 A fan, 58.3 A LRA @ 240 V 3,360 13,992 (from LRA)
Central AC, 1.5-ton 9.0 A + 0.7 A fan, 56.3 A LRA @ 240 V 2,328 13,512 (from LRA)
Sump pump, ½ HP 4.2 A @ 115 V (manufacturer's manual) 483 ~785 (estimated)

Two lessons in that table. First, the ACs: tonnage barely matters to the surge: the 1.5-ton's locked-rotor draw is nearly the 2-ton's, because LRA tracks compressor design more than cooling capacity. Second, notice which rows say "(from LRA)" and which say "(estimated)". That split is the whole problem, next.

The number that isn't printed

Starting amps, the surge, appear on AC plates as LRA, and occasionally on freezers. On almost everything else (fridges, pumps, washers) the label gives you running amps and silence. There are three honest ways across that gap:

What not to do: size a generator on running watts alone. The running total tells you what the machine must carry all day; the largest single surge tells you whether it survives the next motor start. Generators fail outages on the second number.

Nameplate math vs. a real outage

Plate math is worst-case math, and a real outage is kinder than the arithmetic in three specific ways:

That is why a real house can run, on an 11,000 W-starting inverter generator, an AC whose plate surge computes to 14 kW: lights dim, the engine hunts for a second, and it holds. The case nameplate math still warns about, correctly, is two motors starting in the same second. Add the two AC plates above together, 58.3 + 56.3 A, roughly 27 kW for an instant, and sag stops rescuing you. Independent thermostats make that coincidence a matter of luck over a long outage. Two things remove the luck: a soft starter on the compressor (planning figure: starting current around 0.4 × LRA, per Hyper / Eltwin application guidance), or load management that staggers motor starts.

Do it with your own plates

The generator sizing calculator accepts the numbers exactly as your labels print them:

  1. Tick the appliances you need through an outage.
  2. On any row, tap custom, switch to Amps (nameplate), and enter the running amps and volts from your plate. Add LRA if it is printed, and the starting figure then comes straight from your equipment, not a typical.
  3. Read the recommendation, and try the soft-starter scenario if an AC is in your list.

Or see it done: open the calculator with a real house loaded: two ACs, twin sump systems, a septic pump and four cold boxes, every figure from plates like the ones in the table above.

Sources & notes